Capacity level measurement and detection
|
|
|
- Continuous measurement or level detection on conductive or insulating products: liquids, granulates, and powders
- Rigid or cable electrodes
- Double Electrode for a non-conducting container
- High temperature extension
Presentation
A measurement or capacity detection channel is made up of :
- A sensor head: Polycarbonate box IP 65,
- A connection fitting (G1 1/2 as standard),
- A rigid or cabled electrode in contact with the product,
- The electronics are fitted in the sensor head or remotely in a leak-tight box with a coaxial cable link.
How it works
The sensor, the tank and the product being measured form a condensor whose capacity depends on how full it is, so variations in the height of the product lead to variations in capacity. This capacity variation is converted into an on/off signal and an analogue signal for continuous level measurement.
Conditions of use to be defined
|
Container
|
Material, product contained, Max pressure, Max temperature, etc
|
|
Sensor
|
Length L, Position on the container
|
|
Output
|
Analogue 4/20A, for continuous measurement
|
|
|
Relay and dead contact for single level detection
|
Technical characteristics
|
Head
|
Polycarbonate box IP 65
|
|
|
Fitting
|
Connector G1 1/2 steel, stainless steel 316L or PTFE
|
|
|
Flanges as requested
|
|
Electrode
|
Rigid
|
Steel or stainless steel 316L bare
|
|
|
|
Insulated PVC, PTFE, Halard, Peek
|
|
|
|
Max length : 3 metres
|
|
|
Cable
|
With bare counterweight
|
|
|
|
With insulated counterweight
|
|
|
|
Max length : 20 metres
|
|
Electronics
|
Detection
|
See Manual DC31R - Output : 1 contact
|
|
|
|
See Manual MC7.3R - Output : 3 contacts
|
|
|
Measure
|
See Manual TC22/25 - Output : 4/20 mA
|
|
|
As standard, it is fitted in the Head *
|
|
Options
|
High-temperature extension
|
|
|
Double electrode for non-conducting container
|
|
* Note : in the event of a problem with the dimensions of the tank, refer to Manual K41 which presents sensors with a smaller head. In this case, the electronics are located in a plastic leak-tight box with a coaxial cable link.
Other references : R28A et R28B
|
Technical manuals
|
|
Manual code
|
|
|
Sensor
|
K41
|
Capacity level sensor
|
|
|
R28A
|
Compact Capacity level detector
|
|
Electronics
|
DC31R
|
Detector / 1 Switch / Power supply 24, 110, 230 VAC or 24 VDC
|
|
|
MR7.3R
|
Detector / 3 Switches/ Power supply 24 VDC
|
|
|
R28B
|
Detector / 1 Switch
|
|
|
TC22/25
|
Detector / 3 Transmitters / output 4-20 mA / power supply 24, 110, 230 VAC or 24 VDC
|
|